Input voltage (Vac) | 230 Vac |
Rack units | |
Output frequency (Hz) | 50 - 60 |
Output voltage | 230 Vac |
Harmonic distorsion (%THD) | <3 |
Phase | Single |
Power (kVA) | 2 |
Power (W) | 1800 |
Technology | On-line |
Installation | Tower |
POWER (VA) | 2000 |
Input frequency (Hz) | 50 - 60 |
Input power factor | 0,99 |
Output power factor | 0,9 |
Wave form | Pure sine wave |
Signalling | Fault, Low battery voltage, Overload, Operated batteries |
Expandable backup time | yes |
Connection | |
IP rating | IP20 |
BACKUP TIME (min) | 10 |
Overload | 1s - 120% |
By-pass | |
Transfer time (ms) | 0 |
Crest factor | 3 ÷ 1 |
Protections | Excessive battery discharge |
Standard provided equipment | Output cable |
Audible noise at 1m (dBA) | <55 |
Working temperature (°C) | 0 +40 |
Parallel connection | No |
Communication | USB |
Information on the display | Remaining backup time |
EPO - Emergency power off | yes |
Recharge time | 7h to 90% of full capacity |
Battery type | Sealed lead acid, maintenance-free |
Standards | EN 61000-4-2, EN 61000-4-4, EN 62040-1, EN 61000-4-3, EN 61000-4-5 |
Warranty | 2 Year |
Package quantity (pieces) | 1 |
Width (mm) | 190 |
Height (mm) | 328 |
Depth (mm) | 425 |
Weight (Kg) | 21 |
Enter your details, we will reply as soon as possible.
All fields marked with * are required
Technical assistance service for professionals
from Monday to Friday: 10.00 AM - 12.00 PM / 3.00 PM - 6.00 PM
For technical assistance on KERT products please call
+39 0423 650707
Telegram contacts:
@Kert_service
Consulting on purchase of KERT products, services and solutions
info@kert.it